Specific conductance 7000 umhos.
Boiler water hardness ppm.
Only relatively wide ranges can be given as to maximum levels of alkalis salt silica.
Presented by cleaver brooks steve connor bill hooke.
Total hardness 0 3 ppm.
A boiler that makes up 4000 gal day of water having 100 ppm of hardness has a potential of accumulating over 1000 pounds of scale per year.
Therefore good internal boiler water treatment programs are necessary.
The below table is the total dissolved solids or tds alkalinity and hardness versus boiler pressure.
A serious loss of boiler efficiency and possibly boiler failure.
Total hardness 1 ppm maximum.
The hardness of water is caused by calcium and magnesium ions which will vary greatly throughout the country depending on the source.
For boiler water however a hydrometer can be used to obtain an approximate measurement of the dissolved solids since for boiler water each increase of 0 000 1 relative density at 15 5 c is approximately equal to 110 ppm.
Most boiler systems have sodium zeolite softened or demineralized makeup water.
It is desirable to keep the concentration of phosphates in the water to 30 50 ppm in order for complete reaction of the phosphates with the calcium hardness entering the boiler through the feedwater.
Total alkalinity 600 ppm maximum.
Ph 8 3 10 0.
Boiler water parameters upto 20 kg cm2 21 kg cm2to 39 kg cm2 40kg cm2 59kg cm2 unit total hardness not detectable not detectable not detectable total alkalinity 700 500 300 as ppm caco 3 caustic alkalinity 350 200 60 as ppm caco 3 ph value 11 0 o 12 0 11 to 12 10 5 to 11 0 residual sodium sulphite 30 to 50 20 to 30 ppm as na 2so 3.
In treated waters alkalinity may also be contributed by hydroxide phosphate silicate and.
Alkalinity test in natural waters alkalinity is most commonly the result of bicarbonate and carbonate ions.
In addition hardness salts can precipitate from the boiler water to form sludge and eventually scale which deposits on the internal surfaces of the boiler.
Feedwater hardness usually ranges from 0 01 to 2 0 ppm but even water of this purity does not provide deposit free operation.
Total alkalinity 700 ppm.
Total silica 150 ppm maximum.
Feed water purity requirements therefore can vary widely.
Non volatile toc 1 ppm.
Free oh alkalinity 200 400 ppm.
General guidelines to prevent corrosion and scaling in low pressure boilers are as follows.
First knowing the water source is important whether it is from ponds rivers ground wells or city water.
Scale is a buildup of solid material formed on internal boiler surfaces.